Big Book of Hamworthy Products & Services.

47 01202 662500 | sales@hamworthy-heating.com | hamworthy-heating.com BOILERS Dimensions Dimensions Reference ELT440 ELT510 ELT580 Boiler height A 1208 1208 1208 Boiler length B 1998 1998 1998 Boiler width C 1068 1068 1068 Flue connection height D 674 674 674 Front clearance E 1600 1600 1600 B C 160 A D Return Flow Flue Rear Side Front 150 600 Plan view of clearances E 4 1 2 3 Note: 1) Burner lengths vary by model. 2) T he boiler door including burner should be able to swing open through 90° providing access to the burner head and combustion chamber for cleaning and maintenance. 3) A minimum distance of 200mmmust be maintained between boiler casings. It should be noted that burners vary in length by model and this distance may need increasing. 4) A t least 200mm should be allowed to the side of the boiler for fitting the casing. After fitting the casing, the boiler may be moved closer to the wall, but no closer than 60mm. Note: All dimensions in mm unless otherwise stated.